Anybus® Communicator - EtherNet/IP to Modbus RTU/Serial

Set a Node Address with Rotary Switches

About the Rotary Switch Settings

Tip

Use Windows Calculator (or similar application) to convert between hexadecimal (hex) and decimal (dec).

  • The default node address setting is 000.

  • The node address values are set in hexadecimal (hex).

  • Minimum value is 00.

  • Each node address may only occur once in the network.

  • The node address is read from the center rotary switch x16 to the front rotary switch x1.

  • The rear rotary switch is not used, ensure that it is set to 0.

    abc-com2-rotary-switches-2-center-to-front.png
Before You Begin

Ensure that the Communicator is disconnected from power.

Figure 17. Disconnect Communicator from power
Disconnect Communicator from power


Procedure

Use a screwdriver to change the rotary switch position.

Ensure that the rotary switches engage correctly.

abc-com2-rotary-switch-center-screwdriver.png
Example 2. To set the node address 12 hex = 18 dec
abc-com2-rotary-switches-x2-set-example-012.png
  1. The rear rotary switch A is not used, ensure that it is set to 0.

  2. Set the center rotary switch B to 1 hex.

  3. Set the front rotary switch C to 2 hex.

The center rotary switch B 1 hex = 1 dec and the front rotary switch C 2 hex = 2 dec.

The node address expressed in decimal numbers is therefore 16 x 1 + 2 = 18.



To Do Next

Connect the Communicator to power. See Connect to Power.

Figure 18. Connect Communicator to power
Connect Communicator to power


Result

The set node address is active as soon as the Communicator is powered on.

Note

Changing the address settings on the rotary switches during operation is ignored. For a new address to take effect, power cycle the Communicator.