Anybus® CompactCom 40 - PROFINET IRT IIoT Secure

Modular Device RI

The RI, when implementing a modular device, is generated from the Module IDs as defined in the Modular Device Object (ECh) (see the Anybus CompactCom 40 Software Design Guide) and from the process data mappings as shown in the example below.

Module ID:

0x0000004

Submodule ID:

0x00010203

0x0

0: Mapped to Write PD area

1: Mapped to Read PD area

001

ADI index

02

Number of elements to map

03

ADI start element #

A set of conditions must be fulfilled for the Anybus CompactCom to use the Modular Device RI:

  • The Modular Device object implemented must be of revision 1.

  • Modular device object attributes #11 and #12 must be readable and valid

    • Number of slots must be: 0 < NumSlots <= 256

    • ADIs per slot must be: 0 < AdisPerSlot <= 4096

  • The list with Module Type IDs must contain NumSlots items.