Anybus® CompactCom 40 - PROFINET IRT IIoT Secure

Command Details: AR_Abort_Ind

Category

Extended

Details

Command Code:

19h

Valid for:

Object Instance

Description

This command is optional. The module issues this command to indicate to the host application that an Application Relationship (AR) is aborted (by the application or any other source).

  • Command Details

    Field

    Contents

    Comments

    CmdExt[0]

    AR handle (low byte)

    Handle for the Application Relationship (AR)

    CmdExt[1]

    AR handle (high byte)

    MsgData[0]

    Reason code (low byte)

    Reason code for the offline transition

    Value:

    Reason:

    0

    No reason (unknown reason)

    3

    Out of memory

    4

    Add provider or consumer failed

    5

    Miss (consumer)

    6

    Cmi timeout

    7

    Alarm-open failed

    8

    Alarm-send.cnf(-)

    9

    Alarm-ack-send.cnf(-)

    10

    Alarm-data too long

    11

    Alarm.ind(err)

    12

    Rpc-client call.cnf(-)

    13

    Ar-abort.req

    14

    Re-run aborts existing

    15

    Got release.ind

    16

    Device passivated

    17

    18

    Protocol violation

    19

    NARE error

    20

    RPC-Bind error

    21

    RPC-Connect error

    22

    RPC-Read error

    23

    RPC-Write error

    24

    RPC-Control error

    25

    Forbidden pull or plug after check.rsp and before in-data.ind

    26

    AP removed

    27

    Link down

    28

    Could not register multicast-mac

    29

    Not synchronized (cannot start companion-ar)

    30

    Wrong topology (cannot start companion-ar)

    31

    Dcp, station-name changed

    32

    Dcp, reset to factory-settings

    33

    Cannot start companion AR because of parameter error

    MsgData[1]

    Reason code (high byte)

  • Response Details

    (no data)