Reidentifying Your Product
After successful setting of the Setup Complete attribute in the Anybus Object (01h), the Anybus module asks for identification data from the host PROFINET IO Object (F6h). Therefore, the attributes listed below shall be implemented and proper values returned.
Object/Instance | Attribute | Explanation | Default | Customer sample | Comment |
---|---|---|---|---|---|
PROFINET IO Object (F6h), Instance 1 | #1,Device ID | With this attribute you set the Device ID of the device | Device ID: 0010h | Device ID: YYYYh | This information must match the keys of the “DeviceIdentity” of the GSD-file. Note that the GSD file keyword “VendorName” must correspond to the Vendor ID value. |
PROFINET IO Object (F6h), Instance 1 | #2,Vendor ID | With this attribute you set the Vendor ID of the device | Vendor ID: 010Ch (HMS) | Vendor ID: XXXXh | |
PROFINET IO Object (F6h), Instance 1 | #3,Station Type | With this attribute you set the station type of the device | “CompactCom 40 PIR” | “Cust-PNIO-Dev” | Optional if Application Object, Instance 1, Attribute 9 "Product Name" is implemented. In this case the product name common for all networks will be used as Station Type/Device Type on PROFINET. |
PROFINET IO Object (F6h), Instance 1 | #8, I&M Order ID | With this attribute you set the Order ID that is used in the I&M data | “CompactCom 40 PIR” | “Cust-PNIO-Dev” | This information must match the keys of the “OrderNumber” of the GSD-file. |
PROFINET IO Object (F6h), Instance 1 | #10, I&M Hardware Revision | With this attribute you set the I&M Hardware Revision | (Hardware Rev.) | “0002h” | Optional. This information must match the keys of the “HardwareRelease” of the GSD-file. |
PROFINET IO Object (F6h), Instance 1 | #11, I&M Software Revision | With this attribute you set the I&M Software Revision | (Software Rev.) | “V2.5.3” | Optional. This information must match the keys of the “SoftwareRelease” of the GSD-file. |
PROFINET IO Object (F6h), Instance 1 | #13, I&M Profile ID | With this attribute you set the I&M Profile ID | 0xF600 (Generic device) | API number of profile. | Optional, Only relevant for multi-API implementations like PROFIdrive. |
PROFINET IO Object (F6h), Instance 1 | #14, I&M Profile Specific type | With this attribute you set the I&M Profile Specific typ | 0x0004 (Communication Module) | Profile specific type, defined by profile. | Optional, Only relevant for multi-API implementations like PROFIdrive. |