Anybus® CompactCom 40 - PROFINET IRT IIoT Secure

Object Description

This object defines a standardized way of reporting different types of measurement values (current, voltage, power, energy etc.) from a measuring device.

Each instance, logical device, represents a group of measurement values for one separate measurement device. Physically, measuring devices might be connected to a higher level network directly, or indirectly via a coupling device. To enable host applications to implement either a direct or an indirect measuring device, the Anybus CompactCom object model implies a 1:1 relationship between measuring device (a.k.a. logical device) and instance number, where each instance attribute represent a group of measurement values (see list of instance attributes below). The host application does not have to support all instance attributes listed.The command Get_Attribute_Measurement_List is used towards the host application, to read out which measurement values are supported by a device.

The table below shows an example of how the instances of the Anybus CompactCom object model maps to PROFIenergy. PROFIenergy uses the Object number to address a logical device, while the Measurement ID refers to the actual measurement value.

Instance number

Attribute number

PROFINET

Description

(logical device)

(measurement value)

Obj nr

Measurement ID

1

1

0

1,2,3,31

Logical device #1

#1-Voltage PH-N

#4-Voltage PH-PH

#10-Current

4

4,5,6,32

10

7,8,9,33

2

1

1

1,2,3,31

Logical device #2

#1-Voltage PH-N

#4-Voltage PH-PH

#10-Current

4

4,5,6,32

10

7,8,9,33

3

13

2

10,11,12,36

Logical device #3

#13-Apparent Power

#16-Active Power

#19-Reactive Power

16

13,14,15,34

19

16,17,18,35

See also...