Anybus® CompactCom 40 - PROFINET IRT IIoT Secure

Documentation Considerations

To obtain a certificate, the following information must be present in the customer's user manual:

  1. Behavior of the outputs if IOPS=BAD.

  2. Behavior of the outputs if connection is aborted.

  3. Behavior of the outputs at power on.

The Anybus CompactCom handles these situations in the following ways:

  1. State change to IDLE. The network is informed that the I/O data of the submodule with IOPS=BAD is substituted with zeros (clear). No read process data is updated in the host interface.

  2. State change to WAIT_PROCESS. The network is informed that the I/O data of all submodules is substituted with zeros (clear). No process data is updated in the host interface.

  3. The network is informed that the I/O data of all submodules is substituted with zeros (clear). No process data is updated in the host interface.

  4. A shift register application must use the PA signal to clear outputs when the Anybus CompactCom 40 PROFINET IRT IIoT Secure is not in the state PROCESS_ACTIVE.