Anybus® CompactCom 40 - PROFINET IRT IIoT Secure

Anybus State Machine

The table below describes how the Anybus State Machine relates to the PROFINET network.

Anybus State

Implementation

Comment

WAIT_PROCESS

The Anybus stays in this state until an IO connection with an IO controller is opened.

-

ERROR

Configuration data mismatch, initial parameter error, or error reported from application status register.

See Application Status Register for more information.

PROCESS_ACTIVE

IO connection established with IO controller and valid output data has been provided at least once.

-

IDLE

IO controller with which an IO connection is established is in STOP mode, the IO controller has not provided valid output at least once, or error reported from application status register..

  • Some IO controllers will not provide valid output data in the first cycles following a successful connection.

  • See Application Status Register for more information.

EXCEPTION

Turn module status LED red, to indicate major fault, turn network status LED off, and hold Ethernet MAC in reset.

Some kind of unexpected behavior, for example watchdog timeout. See also instance 1, attribute 7 in Network Object (03h).