Anybus® CompactCom 40 - EtherNet/IP IIoT Secure

Error Code Translation

The Anybus CompactCom error codes are translated to OPC UA status codes as described in the table below.

#

Anybus error code

#

OPC UA status code

Comment

0x02

Invalid message format

0x80020000

BadInternalError

0x03

Unsupported object

N/A

N/A

Not possible to define a generic translation. Depends on the context of the request.

0x04

Unsupported instance

0x80340000

BadNodeIdUnknown

Not possible to define a generic translation. Depends on the context of the request.

0x05

Unsupported command

0x803D0000

BadNotSupported

0x06

Invalid CmdExt[0]

N/A

N/A

Not possible to define a generic translation. Depends on what CmdExt[0] contains.

0x07

Invalid CmdExt[1]

N/A

N/A

Not possible to define a generic translation. Depends on what CmdExt[1] contains.

0x08

Attribute not set-able

0x803B0000

BadNotWritable

0x09

Attribute not get-able

0x803A0000

BadNotReadable

0x0A

Too much data

0x80740000

BadTypeMismatch

0x0B

Not enough data

0x80740000

BadTypeMismatch

0x0C

Out of range

0x803C0000

BadOutOfRange

0x0D

Invalid state

0x80AF0000

BadInvalidState

0x0E

Out of resources

0x80030000

BadOutOfMemory

0x0F

Segmentation failure

0x80020000

BadInternalError

0x10

Segmentation buffer overflow

0x80020000

BadInternalError

0x11

Value too high

0x803C0000

BadOutOfRange

0x12

Value to low

0x803C0000

BadOutOfRange

0x13

Attribute controlled

0x801F0000

BadUserAccessDenied

0x14

Message channel too small

0x80020000

BadInternalError

0x15

General error

0x80010000

BadUnexpectedError

0x16

Protected access

0x801F0000

BadUserAccessDenied

0xFF

Object specific

N/A

N/A

Not possible to define a generic translation. Depends on what Anybus object that is accessed.