Device Status

bit(s)

Name

0

Module Owned

1

(reserved)

2

Configured

This bit shows if the product has other settings than "out-of-box". The value is set to true if the configured attribute in the Application Object is set and/or the module’s NV storage is changed from default.

3

(reserved)

4... 7

Extended Device Status:

Value

Meaning

0000b

Unknown

0010b

Faulted I/O Connection

0011b

No I/O connection established

0100b

Non volatile configuration bad

0101b

Major fault

0110b

Connection in Run mode

0111b

Connection in Idle mode

(other)

(reserved)

8

Set for minor recoverable faults. See Diagnostic Object (02h)

9

Set for minor unrecoverable faults. See Diagnostic Object (02h)

10

Set for major recoverable faults. See Diagnostic Object (02h)

11

Set for major unrecoverable faults. See Diagnostic Object (02h)

12... 15

(reserved)