Anybus® CompactCom 40 - EtherNet/IP IIoT Secure

Class Attributes

By default, three instances (port 1, port 2 and the internal port) are implemented, meaning that two ports are activated.

If port 2 is inactivated in the Port 2 State attribute of the Ethernet Host Object (F9h), only one instance (port 1) should be implemented.

#

Name

Access

Type

Value

1

Revision

Get

UINT

0004h (Object revision)

2

Max Instance

Get

UINT

1 or 3 (Maximum instance number)

3

Number of Instances

Get

UINT

1 or 3 (Number of instances)

6

Maximum ID Number Class Attributes

Get

UINT

7 (The attribute number of the last implemented class attribute.)

7

Maximum ID Number Instance Attributes

Get

UINT

11 (The attribute number of the last implemented instance attribute.)